|
In general, when only one
detector is required in a room or
space, the detector should be
placed as close to the center of
the ceiling as possible. Central
location of the detector is best
for sensing fires in any part of
the room. If a center location
is not possible, the detector may
be placed no closer than 4
inches from the wall, or if
listed for wall mounting, it may
be mounted on the wall.
Wall-mounted detectors should be
located not less than 4 inches
nor more than 12 inches from
the ceiling to the top of the
detector, and at least 4 inches (10
cm) from any corner wall
junction. (NFPA
72-2007)
When air supply and/or air return
ducts are present in a room
or space, the detector(s) should not
be placed in the path of
the air flow supply or return (NFPA 72-2007).
|